HP PH HZ Voltz Amps
1 1/2 1 60 240 9.1
# Description
11-1/2" Bulkhead for fill W/Float Valve
21/2" Bulkhead for Test Line
33/4" Bulkhead for Overflow
4Test Line
# Description
5Pressure Switch
6Suction Shut-off Valve
7Pressure Gauge
8Discharge Shut-Off Valve
# Description
9Tank Drain
10Discharge Check Valve
11Control Panel (Optional)
12Riser Manifold
13System Drain

Performance

GPM 0 20 25 30 35 40 50 60
PSI 48 45 39 34
Request a quote.

H2hOme® solutions are available for purchase through our network of select fire protection distributors. Please fill out the form to contact us for information on our readily available purchasing options.

A Note For Homeowners: Whether you’re building a new home or retrofitting your existing home with a fire sprinkler system, the entire system (including all of its’ components such as the H2hOme®) must be compliant with NFPA 13D residential fire sprinkler code. As such, the system and its components should always be installed and commissioned by a certified fire sprinkler contractor to ensure the system’s proper function and ultimately, the safety of your home. Please contact your local fire sprinkler contractor to see if the H2hOme® is right for your system, and to schedule your install.

  • Please select your H2home™ model. For model specifications, please reference the table down below.
  • Tell us about the job site, your pressure / flow requirements, etc.

H2Home® Model Specifications

MODEL GPM 0 20 25 30 35 40 50 60
H2H425-E01 PSI 26 24 20 18
H2H425-E03 PSI 48 46 39 34
H2H425-A04 PSI 61 57 54 52 50 46 39 37
H2H425-A06 PSI 72 67 65 63 60 58 51 45

NAFA13D Compliant.

NFPA 13D 6.2.1 (2):

Pump motors using ac power shall be rated for 240 V
and wired in accordance with the NEC (NFPA 70).

NFPA 13D 6.2.1 (4):

The pump shall be located not less than 1 ½ in. off the floor.

NFPA 13D 6.2.2 (1):

The test connection shall return water to the tank.

NFPA 13D 6.2.2 (3):

A method for determining the water level in the tank
shall be provided without having to open the tank.